| DATA |
 |
 |
- Maximum value for switching capacity
Tested sample: DA3 1F-12V
No.
of operations: 105
-
- Coil temperature rise (resistive)
Tested sample: DA3 1F-12V,
6 pcs
| Ambient temperature: |
20°C, |
85°C, |
125°C |
| 68°F, |
185°F, |
257°F |
Contact carrying current: 40A
Coil applied voltage:
12V, 14V, 16V DC
- Coil temperature rise (resistive)
Tested sample: DA3 1F-12V,
6 pcs
Ambient temperature: 20°C, 68°F
Contact
carrying current: 20A, 30A, 35A, 40A
coil applied voltage: 12V,
14V, 16V DC
- Distribution of operate/release time
(at nominal voltage)
DA3
1F-12V, 100 pcs
Ambient temperature: 22°C, 72°F
| Operate time
|
 |
| Release time
|
 |
- Distribution of pick-up/drop-out voltage
Tested sample: DA3
1F-12V, 100 pcs.
| Pick-up voltage
|
 |
Distribution of pick-up/drop-out voltage
Tested
sample: DA3 1F-12V, 100 pcs.
| Drop-out voltage
|
 |
- Distribution of voltage drop
Tested sample: DA3 1F-12V, 100 pcs.
Tested
method: at 10A voltage drop
| N.C. contact
|
 |
| N.O. contact
|
 |
- Free-fall test
Test conditions:
Drop height: 2 meters to
concrete surface
Drop direction: 6 directions, each 1 drop
sample:
DA3
Quantity: 6 pcs. 1F-12V
 |
 |
 |
 |
Sample No. 1
direction |
Sample No. 2
direction |
Sample No. 3
direction |
Sample No. 4
direction |
 |
 |
| Sample No. 5 direction |
Sample No. 6 direction |
Test result: No abnormality was observed.
| Sample No. |
No. of Operations |
Pick-up Voltage, V |
Drop-out Voltage,
V |
Contact
Resistance, mW |
Insulation
Resistance |
Breakdown voltage |
| N.C. |
N.O. |
| 1 |
Initial
(at 28°C) |
5.2 |
1.8 |
1.9 |
1.5 |
good |
good |
| 2 |
5.2 |
1.9 |
1.5 |
1.7 |
good |
good |
| 3 |
4.9 |
1.8 |
1.6 |
1.9 |
good |
good |
| 4 |
5.1 |
1.8 |
1.7 |
2.6 |
good |
good |
| 5 |
5.2 |
1.8 |
1.9 |
1.7 |
good |
good |
| 6 |
5.3 |
2.1 |
2.0 |
1.5 |
good |
good |
| 1 |
After
(at 28°C) |
4.7 |
1.6 |
1.7 |
1.4 |
good |
good |
| 2 |
4.9 |
1.8 |
2.2 |
1.7 |
good |
good |
| 3 |
4.4 |
1.5 |
2.5 |
1.6 |
good |
good |
| 4 |
4.7 |
1.6 |
2.2 |
2.3 |
good |
good |
| 5 |
4.8 |
1.6 |
2.5 |
1.6 |
good |
good |
| 6 |
4.7 |
1.7 |
1.7 |
1.6 |
good |
good |
Contact resistance: contact voltage drop (10 A)
Insulation
resistance: 20 MW at 500V DC
| Breakdown voltage: |
Between open contacts: 500 Vrms
Between
contacts and coil: 500 Vrms. |
- Ambient temperature characteristics
Tested sample: DA3 1F-12V, 6
pcs.
|
|